Gas Boiler Pump Runs Continuously: Causes and Troubleshooting

If your gas boiler pump runs continuously, even when the thermostat is not calling for heat, it can be a sign of a problem. This issue can lead to increased energy consumption, higher utility bills, and potentially shorten the lifespan of the pump. Understanding the potential causes and following a systematic troubleshooting process is crucial to resolving this issue effectively.

Causes of Continuous Pump Operation

1. Stuck Relay

A stuck relay can cause the pump to run continuously. This is often suspected, but it is less likely to be the primary cause, as the pump would not shut off intermittently if the relay was truly stuck. Relays used in gas boiler systems typically have a coil resistance of 50-100 ohms and should be checked for proper operation.

2. Faulty Zone Valves

Zone valves with stuck or malfunctioning end switches can keep the pump running, even when the thermostat is not calling for heat. The end switches on Honeywell zone valves typically have a resistance of 1-5 ohms when closed and an open circuit when open. Checking the red wires connecting the zone valves to the aquastat and ensuring they are properly connected is essential.

3. Incorrect Wiring

Improper wiring connections can also cause the pump to run continuously. Verifying that all wires are correctly connected to the aquastat and zone valves, with no loose or damaged connections, is crucial. Common wiring issues include crossed or miswired connections, which can lead to the pump running continuously.

4. Faulty Aquastat

A malfunctioning aquastat can lead to continuous pump operation. Honeywell aquastats used in gas boiler systems typically have a temperature range of 100-220°F and a differential of 10-30°F. Checking the aquastat for proper function, including its temperature setpoints and differential, can help identify if it is the root cause of the issue.

5. Air in the System

Air in the system can cause the pump to run continuously, as the pump tries to circulate the air rather than the water. Ensuring that the system is properly bled and that there are no air leaks in the piping or components is essential.

Troubleshooting Steps

Gas Boiler Pump Runs Continuously

  1. Isolate Zones: Begin by isolating each zone to identify if the issue is specific to one zone or a general system problem. This can be done by manually closing the zone valves one by one and observing the pump’s behavior.

  2. Check Zone Valves: Verify that all zone valves are functioning correctly and that their end switches are not stuck. Use a multimeter to check the resistance of the end switches and ensure they are opening and closing as expected.

  3. Inspect Wiring: Carefully check the wiring connections to the aquastat and zone valves for any signs of damage or improper connections. Ensure that all wires are securely connected and that there are no loose or crossed connections.

  4. Check the Aquastat: Ensure the aquastat is functioning correctly by verifying its temperature setpoints and differential. If necessary, replace the aquastat to rule out a malfunctioning component.

  5. Bleed the System: Bleed the system thoroughly to remove any air that may be causing the pump to run continuously. This can be done by opening the air vents on the radiators or using a manual air vent on the pump.

Technical Specifications

  • Pump Type: Circulator pumps, such as the Taco 007 or Grundfos UPS15-58FC, are commonly used in gas boiler systems. These pumps typically have a power consumption of 45-75 watts and a flow rate of 3-7 gallons per minute (GPM).

  • Aquastat: Honeywell aquastats, such as the L4006A or L8148E, are often used to control the boiler temperature. These aquastats have a temperature range of 100-220°F and a differential of 10-30°F.

  • Zone Valves: Honeywell zone valves, such as the V8043E or V8044E, with 2 red and 2 yellow wires are commonly used in multi-zone systems. These valves have a resistance of 1-5 ohms when the end switches are closed.

References

  1. DoItYourself.com – Circulator pump running almost constantly
  2. TerryLove.com – Circulator pump running continually
  3. Screwfix.com – Central heating boiler pump running continuously